Installing the pressure relief valve
What is going on
The relief valve protects the heating circuit from overpressure and must be sized, placed and discharged correctly.
Likely causes
- Relief valve undersized for boiler input or system pressure rating
- Discharge pipe blocked or exposed to freezing
Check in this order
- Only a licensed professional should install the relief valve.
- Mount the valve upright on the boiler, as close to the boiler as possible.
- Do not install any other valve between the relief valve and the boiler.
- Make sure the valve pressure capacity is at least the maximum heating system pressure rating.
- Make sure the valve BTU/H rating is at least the boiler maximum input.
- Route the discharge pipe so hot water cannot spray the operator or equipment, and end it 50 to 150 mm (2 to 6 in) above the floor or floor drain so discharge is visible.
- Do not connect the discharge pipe where it can freeze, and keep it clear of blockages.
- After filling and pressurizing, lift the lever to test the valve. Replace it right away if it does not work correctly.
Applies to: NCB700 heating circuit relief valve
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation manual, p. 184. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.