The relief valve protects the heating circuit from overpressure and must be sized, placed and discharged correctly.

Likely causes

  • Relief valve undersized for boiler input or system pressure rating
  • Discharge pipe blocked or exposed to freezing

Check in this order

  1. Only a licensed professional should install the relief valve.
  2. Mount the valve upright on the boiler, as close to the boiler as possible.
  3. Do not install any other valve between the relief valve and the boiler.
  4. Make sure the valve pressure capacity is at least the maximum heating system pressure rating.
  5. Make sure the valve BTU/H rating is at least the boiler maximum input.
  6. Route the discharge pipe so hot water cannot spray the operator or equipment, and end it 50 to 150 mm (2 to 6 in) above the floor or floor drain so discharge is visible.
  7. Do not connect the discharge pipe where it can freeze, and keep it clear of blockages.
  8. After filling and pressurizing, lift the lever to test the valve. Replace it right away if it does not work correctly.

Applies to: NCB700 heating circuit relief valve

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation manual, p. 184. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.