Beckett · Boiler troubleshooting
NX burner: setting combustion with an analyzer
What is going on
Start-up air settings from Table 1 are only a starting point. Final air must be set with smoke and CO2/O2 readings.
Likely causes
- New install or nozzle change
- Smoke, soot or poor efficiency
Check in this order
- Drill a 1/4 in. test hole in the flue pipe between the boiler and the barometric damper. Seal it when done.
- Check zero calibration of the head/air plate, then set the pointer: go half a number below the target and come back up to it.
- Run the burner 5 to 10 minutes.
- Turn the head/air screw until you see a trace of smoke (counter-clockwise = more air, clockwise = less).
- Read CO2 (or O2) at that trace-of-smoke point. Example in the manual: 13.5% CO2 / 2.6% O2.
- Add air until CO2 drops 1.5 to 2 points (O2 goes up about 2.0 to 2.7 points). Example: 13.5% down to 11.5% CO2. Smoke must read zero.
- Set draft to the boiler maker's number. Natural draft is usually -0.01 to -0.02 in. w.c. over-fire. Direct vent usually needs no draft setting.
- Chimney vent put the cover on and recheck. If CO2 rises with the cover on, take it off and add air until the reading with the cover on is right.
- Tighten the lower acorn nut and splined nut. Start and stop the burner several times and test the primary and all boiler safety controls.
Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Start-up and initial settings p.14-15; Set combustion with test instruments p.15-16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.