AFG burner at low firing rate: low firing rate baffle
What is going on
At firing rates under about 1.00 GPH the AFG may need the low firing rate baffle (LFRB) to cut air flow and pressure. Weil-McLain calls for it on the WGO-2, WGO-3R and WGO-4R and on the Ultra Oil UO-3 at 0.80 GPH.
Likely causes
- Low firing rate baffle missing where the boiler table calls for it
- Air setting too high for a small nozzle
Check in this order
- Power off before opening the burner.
- Check the boiler maker's burner table for the model. If it calls for the LFRB, make sure it is installed. Do not leave it out.
- Max rate with the LFRB by head F0 up to 0.65 GPH; F3, L1, L2 up to 0.85; F4, F6 up to 0.90; V1 up to 1.00 GPH.
- Re-check the Z dimension if the air tube or nozzle line was changed.
- Set combustion with an analyzer after the change.
Applies to: Beckett AF/AFG oil burners (0.40-3.00 GPH) on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Beckett AF/AFG Burner Manual for Weil-McLain WGO/WTGO/SGO boilers (550-143-079/1224), Low firing rate baffle and Figure 9, p.9; burner spec table p.4-5; Beckett AFG Burner Manual for Weil-McLain Ultra Oil boilers (0225) spec table. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.