Beckett · Boiler troubleshooting
AFG burner on biodiesel: analyzer reads CO2 low
What is going on
Most analyzers have no biodiesel fuel setting, so CO2 is calculated wrong on bio blends.
Likely causes
- Analyzer set to #2 oil while burning a biodiesel blend
Check in this order
- Set the analyzer fuel type to light oil / #2 oil.
- On B100 the analyzer shows CO2 about 0.3% lower than it really is. Add 0.3% to the reading. On B20 the error is under 0.1%.
- Better set up by O2, which is measured directly. For bio blends aim for 4.5 to 5.7% O2 (about 11.3 to 12.3% CO2).
Applies to: Beckett AF/AFG oil burners (0.40-3.00 GPH) on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Beckett AF/AFG Burner Manual for Weil-McLain WGO/WTGO/SGO boilers (550-143-079/1224), Analyzers with biodiesel blends, p.16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.