AFG burner: annual service checklist

Beckett AFG

What is going on

What to do on the yearly service of an AFG burner. Service once a year, more often in dusty places.

Likely causes

  • Dirty filter, strainer or nozzle
  • Worn electrodes or igniter contacts
  • Dirty cad cell lens or blower wheel
  • Sooted flue passages

Check in this order

  1. Turn off all power to the burner first (there may be more than one switch).
  2. Replace the oil line filter. Clean or replace the pump strainer and its gasket/O-ring.
  3. Check the oil lines for leaks, water and sludge.
  4. Replace the nozzle with the exact one the boiler maker specifies.
  5. Clean and check electrodes. Replace if cracked or tips are rounded. Re-check electrode settings.
  6. Clean or replace corroded igniter contacts. Clean the cad cell lens.
  7. Clean the head, air tube, blower wheel, air inlet and static plate. Replace damaged gaskets.
  8. Check motor amps (not over nameplate), wiring, pump pressure and cut-off, primary lockout timing and ignition.
  9. Clean the flue passages and flue pipe. Check the chimney for soot.
  10. Set combustion with instruments and write down the results (myTechnician app with the 7565 control).

Applies to: Beckett AF/AFG oil burners (0.40-3.00 GPH) on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Beckett AF/AFG Burner Manual for Weil-McLain WGO/WTGO/SGO boilers (550-143-079/1224), Perform regular maintenance, p.16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.