Beckett · Boiler troubleshooting
AFG burner: setting combustion with an analyzer
What is going on
How to set the air on an AFG burner so it has reserve air and zero smoke.
Likely causes
- Air setting not done with instruments
- Draft changed since last set-up
- Cover installed after setting (changes the air)
Check in this order
- Run the burner 5 to 10 minutes first.
- Set over-fire draft to the boiler maker's number. Natural draft is usually -0.01 to -0.02 in. w.c. Direct vent usually needs no draft adjustment.
- Close the air down until you get a trace of smoke. Measure CO2 (or O2) there. This is your reference, for example 13.5% CO2 / 2.6% O2.
- Open the air to drop CO2 by 1.5 to 2 points (O2 goes up about 2.0 to 2.7 points). Example: 13.5% down to 11.5% CO2.
- Check smoke again. It must be zero.
- Tighten the air band, shutter and head plate.
- If the burner has a cover, put it on and re-test. If CO2 goes up with the cover on, take it off and open the air a bit more.
- Start and stop the burner several times and test the primary control and boiler safeties.
Applies to: Beckett AF/AFG oil burners (0.40-3.00 GPH) on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Beckett AF/AFG Burner Manual for Weil-McLain WGO/WTGO/SGO boilers (550-143-079/1224), Set combustion with instruments, p.15-16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.