Beckett · Boiler troubleshooting

NX burner: air in the oil line, priming the pump (yellow light)

Beckett NX

What is going on

After a new install, filter change or running out of oil the pump has to be bled. The GeniSys 7505 on the NX has a 4-minute Pump Prime mode that ignores the cad cell.

Likely causes

  • Air in the supply line or pump
  • Tank ran empty
  • New install or filter just changed
  • One-pipe system with the bypass plug installed (or two-pipe without it)

Check in this order

  1. Before any reset look in the chamber. If oil has pooled or the boiler is full of oil vapor, shut off power and oil, let it cool and clean it out first. Never try to relight a hot, vapor-filled chamber.
  2. Open both oil shutoff valves. One-pipe supply: the bypass plug must NOT be in the pump (it ships without it). Two-pipe: install the bypass plug.
  3. Call for heat. Once the burner is running, hold the reset button about 15 seconds until the yellow light comes on, then let go.
  4. During the next ignition sequence (valve-on delay, trial for ignition or ignition carryover), click the button once. The control goes into Pump Prime for 4 minutes.
  5. Open the bleed port and run oil into a container until it comes out with no bubbles, then close it.
  6. Click the button again to leave Pump Prime early, or let the 4 minutes run out.
  7. Set pump pressure to Table 1 and set combustion with an analyzer.

Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Pump Prime p.12; Reset button Table 4 p.13; fuel unit bypass plug p.9; start-up p.14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.