Viessmann · Boiler troubleshooting
Check CO2 and O2 at the boiler vent using the actuator test
What is going on
Used at initial start-up and maintenance. The burner is forced to the lower and upper outputs so the flue readings can be checked at each.
Likely causes
- Venting leak
- Boiler not set for the fuel in use
Check in this order
- Connect a flue gas analyzer to test port A on the vent pipe adaptor.
- Open the gas shut-off valve, start the boiler and create a heat demand.
- Open the service menu (the button combination is not legible in the source text; check the full manual).
- Select the Actuator test menu.
- Select 'Base load OFF' to run the lower output. The display then shows 'Base load ON'. The manual also says the burner runs at its upper output here, which conflicts with the lower output, so confirm the output at the unit.
- Select 'Full load OFF' to run the upper output. The display then shows 'Full load ON'.
- Measure CO2 and O2 at the vent pipe adaptor and record them on the Maintenance Record (p. 113).
- Select 'Full load ON' and confirm with OK. Measure CO2 and O2 again and record them.
- Press OK when done, or exit with the back button.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.