Clean boiler heating surfaces
What is going on
Remove soot and boiler cement buildup from the heating surfaces and collector hood.
Likely causes
- Soot in the flue or on the heating surfaces
- Boiler cement buildup on collector hood and sections
Check in this order
- Follow the shut-down procedure.
- Disconnect the breeching and remove the damper (if used) and draft hood.
- Remove the upper rear jacket panel and turn back the jacket insulation to expose the collector hood.
- Remove the collector hood. Clean excess boiler cement from the hood and cast iron sections.
- Remove the burners from the base of the boiler and clean them per the main burner procedure. Place newspaper in the base to catch soot.
- Clean between the sections with a wire flue brush.
- Remove the paper and soot. Vacuum or brush the base and surrounding area.
- Replace the collector hood and seal it with boiler cement.
- Replace the draft hood, damper (if used) and breeching.
- Replace the insulation and jacket panel.
- Replace the main burners.
Applies to: EG and PEG Series 7 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 71. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.