Zone valve zoning with variable primary flow

SVF 500/600 Series 1

What is going on

For systems that use a variable-flow system pump. Figure 15 shows DHW as a zone. Figure 16 shows optional DHW piping. Check the general zone valve zoning page (p. 23) first.

Check in this order

  1. Install a system circulator capable of the variable flow and head required.
  2. Install the flow/check valve on the boiler outlet to prevent gravity circulation during DHW heating.
  3. If a bypass is used (differential pressure valve or pressure reducing valve), place the system supply temperature sensor after the bypass.
  4. Install a flow switch if system flow could drop below the minimum flow in the Table 5 specification (p. 21 referenced; table is not on these pages).
  5. Install a tee for the flow switch on the boiler return pipe.
  6. Use a bypass pressure regulator or pressure reducing valve in high-flow systems to prevent excessive flow through the heat exchanger.

Applies to: SVF 500/600 boilers with variable primary flow pumping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.