Combustion air interlock (CAI) for motorized ventilation air supply
What is going on
A motorized ventilation air supply with or without feedback connects to the CAI plug. The burner does not start until feedback is present.
Check in this order
- Connect the fan or damper to the CAI plug.
- If the device has no feedback, keep the jumper across R and W in place.
- If the device has feedback, remove the jumper.
- Set parameters per the Service Instructions.
Applies to: CAI plug
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Installation Instructions, p. 25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.