Check natural gas input rate
What is going on
Compare measured gas input against the boiler rating label. Run the boiler first and turn off other gas appliances.
Check in this order
- Run the boiler for 10 minutes.
- Turn off all other gas appliances.
- At the gas meter, time how many seconds one cubic foot of gas takes.
- Calculate input as 3600 x 1000 divided by the seconds measured, giving Btuh.
- Compare the result with the boiler rating label input.
Applies to: SlimFit Series 2 natural gas
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 84. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.