Check neutralization unit condensate pH
What is going on
Only applies where a neutralization unit is installed. The granulate is used up as it neutralizes the condensate.
Likely causes
- Condensate pH below 6.5
- Contaminated neutralization unit
Check in this order
- Check condensate pH with a field-supplied pH measuring strip.
- If pH is below 6.5, replace the granulate.
- If the unit is contaminated, rinse it with tap water.
- Refill the granulate up to the red minimum fill marking.
Applies to: Vitodens 200-W B2HB boiler with neutralization unit
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB service instructions, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.