Weil-McLain · Boiler troubleshooting
Install the heating relief valve
What is going on
Relief valve goes on the top boiler water pipe only, never on the boiler outlet. Discharge must be routed safely.
Check in this order
- Mount the relief valve after the hydrostatic test is complete, not before.
- Install it in a ¾" street elbow with a ¾" tee on the top water pipe (air elimination/relief connection).
- Keep the spindle vertical and locate the valve above the heat exchanger.
- Do not place any shutoff valve between the relief valve and the boiler or in the discharge line.
- Pipe the discharge to a safe place, short and the same size as the valve outlet, pitched downward.
- End the discharge plain, not threaded, in material rated for 375°F or greater, at least 6 inches above a floor drain where it is visible.
- Do not run discharge where freezing can occur.
- After filling and pressurizing, lift the lever to test. Replace the valve if it does not discharge freely.
Applies to: Heating side relief valve
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 18 reference, 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.