Check the control fuses

SVF 500/600 Series 1

What is going on

Check the control fuses before replacing the control or major components. A blown fuse can stop the control or other components from working.

Likely causes

  • Blown low voltage fuse (24 Vac)
  • Blown line voltage fuse (120 Vac)

Check in this order

  1. Turn off power to the boiler at the external line switch.
  2. Remove the control access door.
  3. Remove and inspect the seven fuses (items 1, 2 and 3, Figure 78).
  4. Replace only with the specified fuse type and rating. Do not jumper fuses.
  5. Reinstall the control access cover.

Applies to: SVF 500/600 boilers control tray

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 boiler manual, p. 120. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.