Weil-McLain · Boiler troubleshooting
Check the control fuses
What is going on
Check the control fuses before replacing the control or major components. A blown fuse can stop the control or other components from working.
Likely causes
- Blown low voltage fuse (24 Vac)
- Blown line voltage fuse (120 Vac)
Check in this order
- Turn off power to the boiler at the external line switch.
- Remove the control access door.
- Remove and inspect the seven fuses (items 1, 2 and 3, Figure 78).
- Replace only with the specified fuse type and rating. Do not jumper fuses.
- Reinstall the control access cover.
Applies to: SVF 500/600 boilers control tray
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 boiler manual, p. 120. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.