Select heating circuit pump and primary piping
What is going on
Boiler is for closed loop, forced circulation hot water systems only. Pump sizing must be based on accurate flow and pressure drop calculations, including DHW sizing.
Check in this order
- Use standard friction loss method for pipe sizing and keep within boiler min and max flow rates.
- Recommended pumps for WB1B 26 and 35 Grundfos 15-58 (3-speed) or Taco 00R, or equivalent.
- Fit a low-loss header when system flow is above the boiler maximum or below the minimum, or when flow is unknown. Viessmann prefers a low-loss header over closely spaced tees.
- Fit a pressure activated by-pass if any component in the heating circuit can isolate flow to the pump.
- For underfloor heating, install an immersion or strap-on aquastat in the low temperature loop downstream of the mixing valve to switch off the pump and/or boiler.
Applies to: Vitodens 100-W WB1B 26 and 35
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W, WB1B CombiPlus Installation & Service Instructions, p. 36. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.