Wiring boiler return mixing or isolation/modulating valve actuator
What is going on
Install the 120V or 24V valve adaptor and connect the valve actuator through it.
Check in this order
- Disconnect power to the control.
- Mount the 120V or 24V valve adaptor on the DIN rail inside the connection enclosure.
- Insert the plug gS into socket gS on the control.
- Fasten the cable with a tie (see page 30).
- Connect the black wire of the adaptor to terminal aBH on the DIN rail (terminal 8, 9 or 10).
- Connect valve actuator wires to the adaptor terminals as shown in the figures.
Applies to: Vitotronic 100 GC1 valve actuator wiring
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 37. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.