Viessmann · Boiler troubleshooting

Connect combustion air damper through common interface

Vitotronic 100 GC1Vitotronic 300-K MW1S

What is going on

Wire the shared damper on a multiple boiler system, with a field-supplied relay.

Check in this order

  1. Disconnect power to the control and burner.
  2. Wire the damper motor (120 VAC, 5 FLA max.) to the common combustion air device interface.
  3. Wire the proving switch (120 VAC rated) and the 120 VAC supply as shown.
  4. Add the field-supplied relay as shown in the diagram.
  5. Provide disconnect means and overcurrent protection as local codes require.
  6. Select the fuse using the damper manual's current rating.

Applies to: Multiple boiler system, shared damper

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / 300-K MW1S installation, p. 44. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.