Navien · Boiler troubleshooting

Condensate drain installation

NCB700

What is going on

Condensate is acidic, with a pH of 3 to 5. Drain it to a laundry sink or through a neutralizer, or pump it if the drain is far or below the boiler outlet.

Check in this order

  1. Connect a corrosion-resistant drain line (PVC or CPVC) to the 1/2 in NPT fitting at the bottom of the boiler
  2. Do not reduce the fitting or drain line below 1/2 in
  3. Fill the condensate trap with water after installing the drain line
  4. Slope the drain line down at least 1/4 in per foot if no pump is used
  5. Use a condensate pump rated for at least 2 gallons per hour per boiler when a pump is used
  6. Make sure the drain is not blocked or restricted
  7. If a neutralizer is used, inspect it every few months during the first year and replace it as needed
  8. Never let people or animals drink the condensate

Applies to: NCB700 condensate drain

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 191-192. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.