Condensate drain installation
What is going on
Condensate is acidic, with a pH of 3 to 5. Drain it to a laundry sink or through a neutralizer, or pump it if the drain is far or below the boiler outlet.
Check in this order
- Connect a corrosion-resistant drain line (PVC or CPVC) to the 1/2 in NPT fitting at the bottom of the boiler
- Do not reduce the fitting or drain line below 1/2 in
- Fill the condensate trap with water after installing the drain line
- Slope the drain line down at least 1/4 in per foot if no pump is used
- Use a condensate pump rated for at least 2 gallons per hour per boiler when a pump is used
- Make sure the drain is not blocked or restricted
- If a neutralizer is used, inspect it every few months during the first year and replace it as needed
- Never let people or animals drink the condensate
Applies to: NCB700 condensate drain
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 191-192. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.