Viessmann · Boiler troubleshooting

Filling the heating system

Vitocrossal 300 CU3A

What is going on

Fill and vent the heating system with the expansion vessel and fill pressure set correctly.

Check in this order

  1. With the system cold, check the expansion vessel pre-charge.
  2. If pre-charge is below static pressure, top up with nitrogen until it is 1.5 to 3 psi (0.1 to 0.2 bar) above static pressure.
  3. Close the gas shutoff valve.
  4. Open any installed shutoff valves.
  5. Fill the system with water through the boiler drain/fill valve and vent it.
  6. Fill until the fill pressure is 1.5 to 3 psi (0.1 to 0.2 bar) above the expansion vessel pre-charge.
  7. Mark the set pressure on the gauge.
  8. Return shutoff valves to operating position.
  9. Close the drain/fill valve.

Applies to: Vitocrossal 300 CU3A start-up

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A service instructions, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.