Circulator zoning with a DHW zone
What is going on
Each zone gets its own circulator. The boiler circulator must serve only the boiler loop. An AQUA PLUS 60 can be wired as zone 1 at the U-Control.
Check in this order
- Install a separate circulator for each zone.
- Do not use a closed-type expansion tank with an AQUA PLUS water heater.
- Wire the AQUA PLUS 60 aquastat to U-Control P11, pins 4 and 5.
- Wire the DHW circulator to U-Control P2, terminals 1, 4 and 7 (H, N, G).
- Wire the zone pumps to a two-zone circulator relay.
- Wire the circulator relay end switch to U-Control P15, pins 1 and 2.
- Set Priority 1 to DHW system, not DHW direct.
Applies to: Circulator zoning with AQUA PLUS DHW
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.