Weil-McLain · Boiler troubleshooting

Circulator zoning with a DHW zone

Ultra Series 4

What is going on

Each zone gets its own circulator. The boiler circulator must serve only the boiler loop. An AQUA PLUS 60 can be wired as zone 1 at the U-Control.

Check in this order

  1. Install a separate circulator for each zone.
  2. Do not use a closed-type expansion tank with an AQUA PLUS water heater.
  3. Wire the AQUA PLUS 60 aquastat to U-Control P11, pins 4 and 5.
  4. Wire the DHW circulator to U-Control P2, terminals 1, 4 and 7 (H, N, G).
  5. Wire the zone pumps to a two-zone circulator relay.
  6. Wire the circulator relay end switch to U-Control P15, pins 1 and 2.
  7. Set Priority 1 to DHW system, not DHW direct.

Applies to: Circulator zoning with AQUA PLUS DHW

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual 550-100-440/1025, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.