Weil-McLain · Boiler troubleshooting

Check ignition system safety shutoff

SVF Series 1

What is going on

Confirms the ignition lockout works. Done after installation.

Check in this order

  1. Turn the boiler off.
  2. Close the manual gas valve downstream of the gas valve.
  3. Turn the boiler on. It will try to ignite and not light.
  4. Confirm lockout occurs and the display shows Ignition Fault. SVF 1500/2000/2500 retry once; SVF 3000 locks out after one failure.
  5. Clear the lockout with Manual Reset in the Diagnostic Menu.
  6. Open the manual gas valve again.

Applies to: SVF 1500-3000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 89. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.