Weil-McLain · Boiler troubleshooting

Remote target operation (0-10 VDC sets supply temperature)

SlimFit Series 3

What is going on

A remote analog signal sets the supply temperature for any priority.

Check in this order

  1. In the priority menu for the system, set TARGET ADJUST to 0-10v.
  2. In the same menu, set VOLTS FOR MIN (voltage for minimum supply temperature) and VOLTS FOR MAX (voltage for maximum supply temperature).
  3. Check the target temperature versus voltage curve in Figure 56 of the manual.

Applies to: SlimFit Series 3 Control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SlimFit Series 3 boiler manual, p. 68. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.