Weil-McLain · Boiler troubleshooting
Remote target operation (0-10 VDC sets supply temperature)
What is going on
A remote analog signal sets the supply temperature for any priority.
Check in this order
- In the priority menu for the system, set TARGET ADJUST to 0-10v.
- In the same menu, set VOLTS FOR MIN (voltage for minimum supply temperature) and VOLTS FOR MAX (voltage for maximum supply temperature).
- Check the target temperature versus voltage curve in Figure 56 of the manual.
Applies to: SlimFit Series 3 Control
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 68. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.