Weil-McLain · Boiler troubleshooting

Massachusetts sidewall horizontal venting requirements

SVF 500/600 Series 1

What is going on

Required when a sidewall horizontally vented gas boiler is installed in a residential building in Massachusetts, and the vent termination is less than 7 ft above finished grade. The installation must be done by a licensed plumber or gas fitter.

Check in this order

  1. Confirm a licensed plumber or gas fitter is doing the installation.
  2. Install a hard-wired carbon monoxide detector with alarm and battery backup on the floor where the boiler is installed.
  3. Install a battery-operated or hard-wired CO detector with alarm on each additional level of the building served.
  4. If installed in a crawl space or attic, the hard-wired CO detector may go on the next adjacent floor level.
  5. Use CO detectors that meet NFPA 720 and are ANSI/UL 2034 listed and IAS certified.
  6. If detectors cannot all be installed at completion, the owner has 30 days to comply, and a battery-operated CO detector with alarm must be installed in the meantime.
  7. Mount a metal or plastic sign on the building exterior at least 8 ft above grade, directly in line with the vent terminal. Letters must be at least 1/2 inch and must read: GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS.
  8. Leave a copy of all installation, venting and parts instructions with the appliance.

Applies to: Sidewall horizontally vented SVF boilers installed in Massachusetts

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 500/600 Series 1 Boiler Manual, p. 28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.