Viessmann · Boiler troubleshooting

No response from the Modbus gateway

Versatronik 502/502D

What is going on

The master gets no reply from the gateway.

Likely causes

  • Baud/frame settings do not match 9600 8-N-1
  • Rotary dial address is between two positions
  • Communication cables have reversed polarity

Check in this order

  1. Set the connection to 9600 8-N-1.
  2. Check the rotary dial for the device address and make sure it sits on a position, not between two.
  3. Check that A and B polarity matches on all cables.

Applies to: Versatronik 502 / 502D gateway

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 502 & 502D MODBUS manual, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.