Viessmann · Boiler troubleshooting
No response from the Modbus gateway
What is going on
The master gets no reply from the gateway.
Likely causes
- Baud/frame settings do not match 9600 8-N-1
- Rotary dial address is between two positions
- Communication cables have reversed polarity
Check in this order
- Set the connection to 9600 8-N-1.
- Check the rotary dial for the device address and make sure it sits on a position, not between two.
- Check that A and B polarity matches on all cables.
Applies to: Versatronik 502 / 502D gateway
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 502 & 502D MODBUS manual, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.