Viessmann · Boiler troubleshooting
Run a LON participant check
What is going on
Tests communication between the fault manager and the connected system devices.
Check in this order
- Make sure the control unit is set as fault manager (coding 79:1 in the General group).
- Make sure every control unit has its LON participant number.
- Make sure the LON participant list in the fault manager is current.
- From the home screen, open Service and enter the viservice password.
- Open Service functions, then LON participant check.
- Select a participant and start the check with OK.
- Watch for the participant display to flash for about 1 min showing Wink.
- Read the result OK means passed; 'Subscribe ... Check not OK' means failed.
- Use New list to update the participant list before running another check.
Applies to: Vitocrossal 300 CA3B Dual Fuel with LON
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 Dual Fuel Service Instructions, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.