Weil-McLain · Boiler troubleshooting

Check air openings and flue/air piping

ECO Tec Series 3

What is going on

Confirm combustion air is unobstructed and vent and air piping is sealed.

Likely causes

  • Blocked air openings
  • Leaking or deteriorated vent or air piping
  • Contaminants near the air intake

Check in this order

  1. Confirm combustion and ventilation air openings to the room or building are open and unobstructed.
  2. Check operation and wiring of automatic combustion air dampers, if used.
  3. Verify vent discharge and air intake are clean and free of obstructions.
  4. Inspect the vent and air piping for blockage, deterioration or leaks; repair per the vent manufacturer's instructions.
  5. Confirm air inlet piping is connected and sealed.

Applies to: ECO Tec Series 3 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 141. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.