Check flue gas temperature sensor
What is going on
Measure the flue gas sensor resistance and compare it with the flue gas temperature.
Check in this order
- Disconnect the sensor plug in the terminal compartment.
- Measure the resistance at terminals 1 and 2 of the plug.
- Compare the reading with the current flue gas temperature using the table.
- If the values differ significantly, check the installation.
- Replace the sensor if the installation is correct and the reading is still wrong.
Applies to: Flue gas temperature sensor
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200 service instructions, p. 71. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.