Weil-McLain · Boiler troubleshooting
Check burner flame at high and low fire
What is going on
Visual flame check through the observation window, then combustion check with instruments.
Check in this order
- Inspect the flame through the observation window.
- At high fire, the flame should be blue and stable, with the burner surface covered in orange dots.
- At low fire, the flame should be stable, evenly spread over the burner surface and a uniform orange.
- Perform the combustion check with instruments (see startup procedure, page 88).
- If the flame is unsatisfactory or combustion cannot be adjusted within the values in Figure 80, shut down, let the boiler cool, and service the burner.
Applies to: SVF 1500-3000 Series 1 boiler
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF Series 1 boiler manual, p. 96. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.