Viessmann · Boiler troubleshooting
Cleaning the condensate drainage system
What is going on
Keep condensate flowing freely; a blocked drain causes the boiler to shut down on a fault.
Likely causes
- Condensate does not drain freely
- Neutralization granulate exhausted (pH below 6.5)
Check in this order
- Check the neutralization unit pH with a test strip; if below 6.5, replace the granulate.
- If contaminated, rinse the neutralization unit with tap water and refill granulate to the marked level.
- Add water to the flue gas collector through the inspection port and confirm it drains without back pressure.
- Clean the condensate drain hose and pipe at least once a year.
- Release and flush the lower part of the siphon cup, fill it with water and reassemble.
- Reconnect the neutralization system hose to the siphon.
Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 77. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.