Viessmann · Boiler troubleshooting

Cleaning the condensate drainage system

Vitocrossal 300 CA3B Dual Fuel

What is going on

Keep condensate flowing freely; a blocked drain causes the boiler to shut down on a fault.

Likely causes

  • Condensate does not drain freely
  • Neutralization granulate exhausted (pH below 6.5)

Check in this order

  1. Check the neutralization unit pH with a test strip; if below 6.5, replace the granulate.
  2. If contaminated, rinse the neutralization unit with tap water and refill granulate to the marked level.
  3. Add water to the flue gas collector through the inspection port and confirm it drains without back pressure.
  4. Clean the condensate drain hose and pipe at least once a year.
  5. Release and flush the lower part of the siphon cup, fill it with water and reassemble.
  6. Reconnect the neutralization system hose to the siphon.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 77. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.