Set up digital inputs DE1 to DE3
What is going on
Each digital input can be set to one function: heating program changeover, external blocking, external blocking with fault input, external demand with minimum boiler water temperature, fault message input, brief DHW recirculation pump operation, or zone circuit pump operation.
Check in this order
- Use potential-free contacts only.
- Keep safety category II clearance 8.0 mm air and creep path, or 2.0 mm insulation to live parts.
- Select the input function with coding address 3A (DE1), 3B (DE2) or 3C (DE3) in the General group.
- For heating program changeover, assign it to a circuit with D8:1 (DE1), D8:2 (DE2) or D8:3 (DE3) in the Heating circuit group.
- Set the changeover effect with D5 and the changeover duration with F2 in the Heating circuit group.
- For a brief DHW recirculation pump run, close the DE contact with a push button and set the runtime with 3D in the General group.
Applies to: Vitodens 200-W B2HB
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HB service instructions, p. 88. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.