Viessmann · Boiler troubleshooting

Install and check the boiler temperature sensor

Vitotronic 300

What is going on

The boiler water sensor is fitted with the boiler insulation and plugs into socket 3 on the boiler control. Check it by resistance against the temperature.

Check in this order

  1. Disconnect plug in the boiler control terminal compartment.
  2. Measure resistance at terminals 1 and 2 of the plug.
  3. Compare the reading with the actual boiler water temperature using the resistance table.
  4. If the value differs significantly, check the installation and replace the sensor if needed.
  5. Plug the sensor into socket 3 on the boiler control.

Applies to: Boiler temperature sensor, socket 3

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 Installation and Service Instructions, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.