ECO Tec S2 direct-connect piping: temperature rise too low
What is going on
Direct-connect piping (no primary/secondary) only works on the 80/110/150 heating-only models, and the boiler pump must give at least a 20 F rise at high fire.
Likely causes
- System flow higher than the boiler can take
- System head too high for the built-in circulator
- Zoned with circulators (needs primary/secondary)
Check in this order
- Measure supply and return at high fire. Rise should be 20 to 35 F depending on model.
- Under 20 F reduce flow until you get 20 F.
- If the built-in pump cannot meet the system head (Figure 57 p.48), or the system is zoned with circulators, re-pipe primary/secondary.
- Zone valve systems need a by-pass pressure regulator.
Applies to: ECO Tec 80/110/150 Series 2 heating only
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Direct connect system piping p.47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.