ECO Tec S2 direct-connect piping: temperature rise too low

Weil-McLain ECO Tec Series 2

What is going on

Direct-connect piping (no primary/secondary) only works on the 80/110/150 heating-only models, and the boiler pump must give at least a 20 F rise at high fire.

Likely causes

  • System flow higher than the boiler can take
  • System head too high for the built-in circulator
  • Zoned with circulators (needs primary/secondary)

Check in this order

  1. Measure supply and return at high fire. Rise should be 20 to 35 F depending on model.
  2. Under 20 F reduce flow until you get 20 F.
  3. If the built-in pump cannot meet the system head (Figure 57 p.48), or the system is zoned with circulators, re-pipe primary/secondary.
  4. Zone valve systems need a by-pass pressure regulator.

Applies to: ECO Tec 80/110/150 Series 2 heating only

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Direct connect system piping p.47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.