Viessmann · Boiler troubleshooting
Field test the fixed high limit (CSD-1, where required by law)
What is going on
Viessmann is not responsible for damage the test can cause by overheating the system. Three simulations are described. Simulation 1 and 2 test the fixed high limit with the burner running. Simulation 3 tests the control fault produced by a wiring fault on the limit.
Check in this order
- Simulation 1 close the boiler valve and jumper across the flow switch.
- Simulation 1 run the boiler at high fire. The boiler should shut down via the coding card (on B2TB models set coding address 06 to maximum), but the temperature should keep rising until the fixed high limit trips.
- Simulation 1 once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.
- Simulation 2 throttle the boiler valve so the burner runs with as little flow as possible.
- Simulation 2 run the boiler to high fire using the relay test.
- Simulation 2 when the burner shuts down on the electronic limit, close the ball valve to stop the flow.
- Simulation 2 the boiler temperature should continue to rise and trip the fixed high limit.
- Simulation 2 once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down safely.
- Simulation 3 disconnect one of the wires on the limit switch. This produces a control fault that needs a manual reset.
- Confirm the boiler locks out and requires manual reset after each simulation.
Applies to: Vitodens 200-W B2HA boilers where CSD-1 testing is required
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA service instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.