Weil-McLain · Boiler troubleshooting

Check air pressure switch setting with manometer

CGi Series 5

What is going on

Confirm the air pressure switch closes at the correct draft reading during ignition attempts.

Likely causes

  • Blocked or kinked hoses
  • Blockage in the inducer outlet or block assembly
  • Loose inducer wheel or wrong inducer rpm
  • Inducer back plate not sealed

Check in this order

  1. Keep boiler water at 100 F or cooler before starting so readings are valid.
  2. Confirm the red hose goes from the black (+) barb to the right side collector hood tapping, and the white hose goes from the tan (-) barb to the left side tapping between flue collector and inducer. On CGi-7 and -8 the red hose goes to the Y-fitting on both (+) barbs.
  3. Remove the air pressure switch hoses from the switch (or Y-fitting on dual switches).
  4. Install tees and tubing to the inclined manometer.
  5. Turn off gas and call for heat. The inducer runs but burners do not light.
  6. Check for 24 VAC between both air pressure switch terminals.
  7. If the manometer reads below the switch setpoint, check hoses, inducer outlet, inducer wheel, rpm, back plate seal and block assembly.
  8. If the manometer reads above setpoint but there is no 24 VAC across the switch terminals, replace the air pressure switch.
  9. When correct, remove the tees and reinstall the hoses.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.