Viessmann · Boiler troubleshooting

Close the control unit cover

Vitodens 200-W B2HB

What is going on

Reinstall the control board cover after wiring is complete.

Check in this order

  1. Install the cover onto the control board.
  2. Flip the control board back into position.
  3. Secure the locking tabs as shown in the manual.

Applies to: Models 45, 57, 160, 199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB installation instructions, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.