Viessmann · Boiler troubleshooting
Check boiler water temperature sensor, DHW tank sensor or supply/low-loss header sensor
What is going on
Check sensor resistance and compare with the curve. Sensor type is NTC 10 kΩ. Only one supply temperature sensor or low-loss header sensor may be used.
Likely causes
- Faulty boiler water temperature sensor
- Faulty DHW tank temperature sensor
- Faulty supply or low-loss header temperature sensor
Check in this order
- Drain the boiler before replacing a sensor, as the sensors are immersed in heating water (scald risk).
- Boiler temperature sensor remove lead to sensor and measure resistance.
- DHW tank sensor pull plug from cable harness at control unit and measure resistance.
- Supply or low-loss header sensor pull plug X3 and measure across terminals X3.4 and X3.5.
- Compare values with the curve and replace the sensor if deviation is severe.
Applies to: Boiler temperature sensor, DHW tank sensor, supply or low-loss header sensor
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 86. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.