Viessmann · Boiler troubleshooting

Check boiler water temperature sensor, DHW tank sensor or supply/low-loss header sensor

Vitodens 200-W B2HA

What is going on

Check sensor resistance and compare with the curve. Sensor type is NTC 10 kΩ. Only one supply temperature sensor or low-loss header sensor may be used.

Likely causes

  • Faulty boiler water temperature sensor
  • Faulty DHW tank temperature sensor
  • Faulty supply or low-loss header temperature sensor

Check in this order

  1. Drain the boiler before replacing a sensor, as the sensors are immersed in heating water (scald risk).
  2. Boiler temperature sensor remove lead to sensor and measure resistance.
  3. DHW tank sensor pull plug from cable harness at control unit and measure resistance.
  4. Supply or low-loss header sensor pull plug X3 and measure across terminals X3.4 and X3.5.
  5. Compare values with the curve and replace the sensor if deviation is severe.

Applies to: Boiler temperature sensor, DHW tank sensor, supply or low-loss header sensor

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 112, 150, 399, 530 service instructions, p. 86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.