Weil-McLain · Boiler troubleshooting

Monthly piping, relief valve and air vent checks

CGa Series 4CGi Series 5EG Series 7PEG Series 7LGB Series 2 & 3

What is going on

Monthly inspection of piping, relief valve and automatic air vents.

Likely causes

  • Leaks from fittings, circulators or relief valve
  • Relief valve weeping
  • Air vent not operating freely

Check in this order

  1. Look for leaks around piping, circulators, relief valve and fittings; have any leak repaired right away by a qualified technician.
  2. Do not use petroleum-based cleaning or sealing compounds in the system.
  3. Check the relief valve and its discharge pipe for weeping or leakage.
  4. If the relief valve often weeps, contact a technician. Water boilers: suspect the expansion tank. Steam boilers: suspect a limit control set too high or system problems.
  5. Remove the cap from each automatic air vent and press the valve lightly with a screwdriver tip; it should move freely without leaking.
  6. Put the cap back on fully, then loosen it one turn so the vent can work.
  7. Have any vent that does not work correctly replaced.

Applies to: All boilers in this manual

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.