Weil-McLain · Boiler troubleshooting
Monthly piping, relief valve and air vent checks
What is going on
Monthly inspection of piping, relief valve and automatic air vents.
Likely causes
- Leaks from fittings, circulators or relief valve
- Relief valve weeping
- Air vent not operating freely
Check in this order
- Look for leaks around piping, circulators, relief valve and fittings; have any leak repaired right away by a qualified technician.
- Do not use petroleum-based cleaning or sealing compounds in the system.
- Check the relief valve and its discharge pipe for weeping or leakage.
- If the relief valve often weeps, contact a technician. Water boilers: suspect the expansion tank. Steam boilers: suspect a limit control set too high or system problems.
- Remove the cap from each automatic air vent and press the valve lightly with a screwdriver tip; it should move freely without leaking.
- Put the cap back on fully, then loosen it one turn so the vent can work.
- Have any vent that does not work correctly replaced.
Applies to: All boilers in this manual
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.