Viessmann · Boiler troubleshooting

Test gas solenoid valve seals for leaks

Vitocrossal 200 CI2

What is going on

On 750/1000 MBH burners the burner control unit automatically checks both coaxial safety valves for leaks at startup. If there are no leaks, the burner starts and runs normally. Replacement steps are not given on these pages.

Likely causes

  • Leaking coaxial safety valve on the gas solenoid valve

Check in this order

  1. Start the burner so the control unit runs the automatic seal test.
  2. If the test passes, the burner starts and runs normally.
  3. Check the sealing points of the gas solenoid valve for leaks after the burner starts.

Applies to: Vitocrossal 200 CI2 750/1000 MBH burners

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.