Viessmann · Boiler troubleshooting

Check boiler, DHW tank and flow or low-loss header temperature sensors

Vitodens 200-W

What is going on

Check the resistance of these NTC 10 kOhm sensors and compare it with the temperature curve. Drain the boiler before replacing the boiler temperature sensor because it sits in heating water and there is a scalding risk.

Likely causes

  • Sensor out of tolerance

Check in this order

  1. Boiler temperature sensor A remove the lead to the boiler water temperature sensor and check the resistance.
  2. DHW tank temperature sensor pull plug from the cable harness at the control unit and check the resistance.
  3. Supply or low-loss header sensor pull plug X3 from the control unit and check the resistance across terminals X3.4 and X3.5. Only one of these sensors may be used.
  4. Compare the readings with the temperature curve.
  5. Replace the sensor if the deviation is severe.

Applies to: Vitodens 200-W B2HB

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HB service instructions, p. 84. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.