Viessmann · Boiler troubleshooting
Leak test on boiler and flue gas path
What is going on
Check gaskets and components that carry flue gas for leaks while the boiler runs.
Likely causes
- Failed gasket on burner plate
- Failed seal on flue gas collector
- Leak at heating water connections or low-water indicator connections
Check in this order
- Check the heating system pressure (8 to 160 psi).
- Inspect gaskets with an inspection mirror during operation, or with a dew point hygrometer at full load.
- Remove thermal insulation parts if needed.
- Look for condensate traces on the flue gas collector or insulation. These also show leaks.
- Check connections for control equipment and the minimum pressure monitor for leaks.
- Check all heating water connections for leaks about every 500 operating hours.
Applies to: Vitocrossal 300 CA3B 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B service instructions, p. 11, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.