Leak test on boiler and flue gas path

Vitocrossal 300 CA3B

What is going on

Check gaskets and components that carry flue gas for leaks while the boiler runs.

Likely causes

  • Failed gasket on burner plate
  • Failed seal on flue gas collector
  • Leak at heating water connections or low-water indicator connections

Check in this order

  1. Check the heating system pressure (8 to 160 psi).
  2. Inspect gaskets with an inspection mirror during operation, or with a dew point hygrometer at full load.
  3. Remove thermal insulation parts if needed.
  4. Look for condensate traces on the flue gas collector or insulation. These also show leaks.
  5. Check connections for control equipment and the minimum pressure monitor for leaks.
  6. Check all heating water connections for leaks about every 500 operating hours.

Applies to: Vitocrossal 300 CA3B 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B service instructions, p. 11, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.