Glow Brand · Boiler troubleshooting
Display is blank
What is going on
Nothing on the LCD at all.
Likely causes
- No power to the boiler
- Breaker off
- ICB 5 A fuse blown
- Display cable loose
Check in this order
- Confirm the boiler is on a live 120 V circuit and the breaker is on.
- Look for the LED on the ICB. If it is off, check the 5 A fuse inside the ICB (replace only with the same B-221 5 A 250 V type).
- If the LED is on, check the cable from the ICB to the display.
Applies to: B85, B120, B160 (NG and LP)
More boiler guides
Related
Glow Brand error codes · Glow Brand parts · Glow Brand tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, 13.2.1 p.67. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.