Viessmann · Boiler troubleshooting

Check and clean the burner tube and gauze

Vitocrossal 300 CA3B Dual Fuel

What is going on

Clean or replace the burner gauze and check the insulation ring. Use new gaskets on reassembly.

Likely causes

  • Contamination of the burner tube

Check in this order

  1. Dismantle the burner first (see the burner dismantling steps).
  2. Undo the 6 screws on the insulation ring (1.1 lb.in / 1.5 Nm on refit) and remove the ring.
  3. Unscrew the burner gauze assembly; vacuum it or replace it (7.5 lb.ft / 10 Nm on refit).
  4. Replace all gaskets and reassemble the burner tube and burner in reverse order (7.5 lb.ft / 10 Nm).
  5. Do not let insulation fibres stick to the burner tube or fall into the combustion chamber.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 71. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.