Weil-McLain · Boiler troubleshooting

Direct exhaust boiler room air openings

SlimFit Series 2

What is going on

Size the boiler room openings for combustion and ventilation air when the boiler uses inside air. Openings must also handle the air movement of any exhaust fans in the space.

Likely causes

  • Space under negative pressure from exhaust fans or mechanical ventilation
  • Tight construction without outside air openings

Check in this order

  1. Use Figure 25 to pick the case that matches the room (with or without other appliances, and single or two openings).
  2. Size each opening as free area after louver or grille reduction.
  3. If only one opening is used, it must open directly to outdoors (not to an interior space), have its top within 12 in of the ceiling, and have free area at least equal to the total area of all equipment vent connectors in the space.
  4. If the space volume is at least 50 cu ft per 1,000 Btuh of total appliance input, no openings are needed, provided the building is not tight construction.
  5. Example 1,500 MBH total input needs at least 75,000 cu ft (50 x 1,500).

Applies to: Category IV direct exhaust installations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit 1000-2000 Series 2 boiler manual, p. 30-31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.