Weil-McLain · Boiler troubleshooting
Assemble solvent-cement vent and air piping
What is going on
Dry-fit the full run first, then cement each joint so it seals and does not leave excess cement inside.
Check in this order
- Work from the boiler toward the termination and do not exceed the maximum lengths for air or vent.
- Install pipe reducers where needed at the boiler and at the termination assembly.
- Cut pipe to length, deburr inside and outside of each end, and chamfer the outside of each end.
- Clean all pipe ends and fittings, then dry them.
- Dry-assemble the full vent or air run before cementing any joint.
- For each joint, apply primer to both the pipe end and fitting socket while it is still wet.
- While primer is damp, apply approved cement evenly to both surfaces, then apply a second coat.
- Insert the pipe fully with the cement still wet, twisting about 1/4 turn.
- Wipe excess cement and confirm a smooth bead shows around the whole joint.
- Install pipe supports as shown in Figure 76 on page 70.
Applies to: Ultra vent and air piping (PVC/ABS)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 71. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.