Massachusetts sidewall horizontal vent: required safety items

Ultra Series 4

What is going on

Applies to sidewall horizontally vented gas equipment in residential buildings where the vent terminal is less than 7 feet above finished grade, including over decks and porches. Boiler must be installed by a licensed plumber or gas fitter. Listed equipment in NFPA 54 Chapter 10 and product-approved equipment in a separate structure are exempt.

Check in this order

  1. Confirm a hard-wired CO detector with alarm and battery backup is installed on the floor where the boiler is located.
  2. Confirm a battery-operated or hard-wired CO detector with alarm is installed on each additional level served.
  3. If the boiler is in a crawl space or attic, the hard-wired detector may go on the next adjacent floor.
  4. If detectors cannot be completed at install, the owner has 30 days to complete them, and a battery-operated CO alarm must be installed in the meantime.
  5. Use CO detectors that meet NFPA 720, are ANSI/UL 2034 listed and IAS certified.
  6. Mount a metal or plastic sign on the outside wall at least 8 feet above grade, directly in line with the vent terminal. Lettering must be at least 1/2 inch and must warn that the gas vent is directly below and must be kept clear.
  7. Use only plastic vent pipe that the boiler manufacturer allows, that is listed to a venting standard, and that is accepted by the state board.
  8. Leave all installation, venting and parts instructions with the appliance.

Applies to: Ultra boilers with sidewall vent in Massachusetts

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 65. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.