Viessmann · Boiler troubleshooting
Disconnecting the burner
What is going on
Prepare the burner for removal by disconnecting its electrical connections.
Check in this order
- Close the gas shut-off valve.
- Switch off the main circuit breaker or power supply and lock it out.
- Remove the left side panels of the boiler.
- Disconnect the power cable plug, then the burner cables and plugs from the burner control unit.
- Disconnect the KM-BUS connector from the burner control unit.
- Pull the burner out of the burner casing.
Applies to: Vitocrossal 300 CA3B 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.