Boiler activation contact for external modulation controller
What is going on
Wiring and behaviour of the boiler activation dry contact on plug aVH (Vitocrossal 300, CT3).
Check in this order
- Connect a dry contact across terminals 2 and 3 of plug aVH.
- Contact closed the preheat function for follow-up boilers runs first (coding 2b). After preheat, burner stages or modulation can be switched externally.
- Contact closed boiler water temperature is capped by the preset maximum or the mechanical high limit. The set-point is chosen with coding 9b.
- Contact open the isolation valve closes after about 5 minutes (coding 2C). External burner stage override is not possible and no minimum temperature is held.
- On multi-boiler systems the lead boiler contact must stay closed at all times.
Applies to: Vitocrossal 300 with external modulation controller
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitotronic 100 GC1 installation manual, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.