Viessmann · Boiler troubleshooting

Change the adjustable high limit

Vitotronic 100 GC1

What is going on

Factory setting is 95 °C / 203 °F. Limit range is set by breaking off stop cams on the selector dial. Range A gives 75 to 195 °C (167 to 203 °F), range A and B gives 75 to 100 °C (167 to 212 °F), and range A, B and C gives 75 to 110 °C (167 to 230 °F). Note the setting of coding address 06 after changing.

Check in this order

  1. Disconnect power to the control and burner.
  2. Lever out and remove the selector knob 'R' behind the hinged cover with a suitable screwdriver.
  3. Break off the cams for the unwanted ranges from the stop dial with pointed pliers.
  4. Refit selector knob 'R' so the marking sits in the centre of the selected range.
  5. Record the setting of coding address 06.

Applies to: Vitotronic 100 GC1 adjustable high limit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.