Viessmann · Boiler troubleshooting
Replace ignition unit
What is going on
The ignition unit is mounted on the burner. Reinstall in reverse order.
Check in this order
- Pull the connecting cable from the ignition unit.
- Pull the ignition cables from the ignition unit.
- Undo the ignition unit mounting screws and remove the unit.
- Install the new unit in reverse order.
- Torque the mounting screws to 13 lb.in (1.5 Nm).
Applies to: CA3B Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.